PIPE FREEZE PROTECTION HEAT TRACE CABLES COMPARISON PAGE

Self Regulating Cables Mineral Insulated Cable Assemblies
image image image image
TT Series CO Series Copper Sheath HDPE Overjacket
Wattage Output: variable along
heated length
variable along
heated length
constant along
heated length
constant along
heated length
Custom Built To Order: no no yes yes
Operating Voltages: 120 120 - 277 12 - 480 12 - 480
Watts per Linear Foot1: 5 6 1 - 24 1 - 14
Max. Maintenance Temperature: 150°F 150°F 300°F 158°F
Max. Exposure Temperature: 185°F 185°F 392°F 194°F
Max. Circuit Length2: 125' 450' 400' 400'
Approvals: UL UL UL UL
Ordinary Locations: yes yes yes yes
Factory or Field Terminated3: field field factory factory
Power Connection Kit: PCK-TT PCK-CO N/A N/A
Typical Life Expectancy: 8 - 10 years 8 - 10 years N/A N/A
Warranty: 1 year 3 years 20+ years 20+ years
Suggested M.S.R.P
Per Linear Foot:
starting at
$3.10
starting at
$4.10
starting at
$4.90
starting at
$5.50

1. Wattage outputs depend upon the operating voltage being applied to the cable. Self regulating cables will also vary their wattage output along the heated length in response to changes in ambient temperature.

2. Maximum circuit lengths depend upon the cable's wattage output, and for SR cable and MI cables only, the operating voltage. Please review individual cable datasheets.

3. Factory terminated cables undergo quality testing before shipping from the factory. Standard cold leads are 20' and can be customized to any length.