PROCESS HEAT TRACE CABLE COMPARISON TABLE
|
| Constant Wattage Cables
|
| Self Regulating Cables
|
| Mineral Insulated Cable Assemblies
|
|
|
|
|
|
|
|
|
|
| |
|
| PFSeries
| PT Series
|
| IN Series
| HT Series
|
| Copper Sheath
| HDPE Overjacket
| Alloy 825 S.S. Sheath |
| Wattage Output:
| constant along heated length
| constant along heated length
|
| variable along heated length
| variable along heated length
|
| constant along heated length
| constant along heated length
| constant along heated length |
| Custom Built To Order:
| no
| no
|
| no
| no
|
| yes
| yes
| yes |
| Operating Voltages:
| 120 - 480
| 120 - 480
|
| 120 - 277
| 120 - 277
|
| 12 - 480
| 12 - 480
| 12 - 480 |
| Watts Per Linear Foot1:
| 2 - 14 | 2 - 10
|
| 3, 5, 8, 10
| 5, 10, 15
|
| 1 - 24
| 1 - 14
| 1 - 50 |
| Max. Maintenance Temperature:
| 200°F
| 400°F
|
| 150°F
| 250°F
|
| 300°F
| 158°F
| 1022°F
|
| Max. Exposure Temperatures:
| 400°F
| 550°F
|
| 185°F
| 366°F
|
| 392°F
| 194°F
| 1238°F
|
Max. Circuit Length2:
| up to 780'
| up to 480'
|
| up to 660'
| up to 480'
|
| up to 400'
| up to 400'
| up to 400'
|
| Approvals:
| FM
| FM
|
| FM, CSA, UL
| FM, CSA, UL
|
| UL
| UL
| UL |
| Ordinary Lcoation:
| yes
| yes
|
| yes
| yes
|
| yes
| yes
| yes |
| Class I Div 1:
| no
| no |
| yes
| yes
|
| yes
| yes
| yes |
| Class I Div 2:
| yes
| yes |
| yes
| yes
|
| yes
| yes
| yes |
| Factory or Field Terminated3:
| field
| field
|
| field
| field
|
| factory
| factory
| factory
|
| Power Connection Kit:
| PCK-PT/PF
| PCK-PT/PF
|
| PCK-IN
| PCK-HT or PCK-HLC
|
| N/A
| N/A
| N/A |
| Typical Life Expectancy:
| 10 - 15 years
| 10 - 15 years
|
| 8 - 10 years
| 8 - 10 years
|
| 20+ years
| 20+ years
| 20+ years |
| Warranty:
| 10 years
| 10 years
|
| 10 years
| 10 years
|
| 10 years
| 10 years
| 10 years |
Suggested M.S.R.P Per Linear Foot:
| starting at $8.50
| starting at
$10.60
|
| starting at
$6.80
| starting at
$13.40
|
| starting at
$4.90
| starting at
$5.50
| starting at
$10.50
|
1. Wattage outputs depend upon the operating voltage being applied to the cable. Self regulating cables will also vary their wattage output along the heated length in response to changes in ambient temperature.
2. Maximum circuit lengths depend upon the cable's wattage output, and for SR cable and MI cables only, the operating voltage. Please review individual cable datasheets.
3. Factory terminated cables undergo quality testing before shipping from the factory. Standard cold leads are 20' and can be customized to any length.
|
|